Output |
No. Of DC outputs (+Ve and -ve) |
1 |
DC output cable size |
upto 300 sqmm |
DC output cable exit |
IP 68 polyamide gland |
Output cable termination |
Bolt type |
Interface connectionRS 485 cable |
2x2C twisted pair shielded0.5 sqmm RS 485 standard |
RS 485 cable IN/OUT(at 80 ° with 1,000 W/m2) |
IP 68 polyamide cable gland |
Switch ON/OFF status |
Available (Optional) |
SPD ON/OFF status |
Available (Optional) |
Monitoring Device |
Measuring parameters |
Input current, System voltage,Internal temperature |
Input current monitoring |
Each string / 2:1 monitoring |
Monitoring device |
TRICHECK 8 |
Type of monitoring |
Shunt |
Voltage measurement accuracy |
(+/-) 0.2% |
Current measurement accuracy |
<1% |
Power consumption |
<3W |
On-board temperature measuringrange |
0-120°C |
Digital Ports |
2 |
Shield clamp for earthing provided |
Yes |
Analog ports |
2 |
Communication interface |
MODBUS RS 485 |
MODBUS ID |
Defined by DIP switches /Firmware |
Logs |
MODBUS RTU |
Baud rate |
2400bps / 4800bps / 9600bps /19200bps |
Maximum no. of devices on bus |
240 |
Operating temperature |
(-10) to 70°C |
Applicable standards |
IEC 61326-1-2005 |